SDM630 MCT M-bus V2 MID 3-phase electricity meter
With M-bus, pulse output suitable for logging.
Modular device for DIN rail 35mm, width: 4 modules (72.3 mm), the display shows Volts, Watts, Apmeres, Frequecy, Power factor and more.
MID certification makes it possible to use for billing purposes.
Specifications
5.1 Measured Parameters
The unit can monitor and display three phase four wire (3p4w) supply.
5.1.1 Voltage and Current
Phase to neutral voltages 100 to 289V a.c.
Voltages between phases 173 to 500V a.c.
Percentage total voltage harmonic distortion (THD%) for each phase to N
Percentage voltage THD% between phases
Current THD% for each phase
Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Power 0 to 3600 MW
Reactive Power 0 to 3600 MW
Volt-amps 0 to 3600 MVA
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for three phase supplies only)
Energy Measurements
Imported active energy 0 to 999999.99 kWh
Exported active energy 0 to 999999.99 kWh
Imported reactive energy 0 to 999999.99 kVArh
Exported reactive energy 0 to 999999.99 kVArh
Total active energy 0 to 999999.99 kWh
Total reactive energy 0 to 999999.99 kVArh
Measured Inputs
Maximum terminal opening for power cables is 2,5 mm2
Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) ±1% of range maximum
Total harmonic distortion 1% up to 31st harmonic
Temperature co-efficient Voltage and current = 0.013%/°C typical
Active energy = 0·018%/°C, typical
Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.
Interfaces for External Monitoring
Three interfaces are provided:
M-bus
One fixed pulse output 3200 Imp/kWh
M-bus parameters are configured through the Set-up screens.
Pulse Relay Output
The pulse relay output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 ms.
Relay Rating 240V ac 50mA
M-bus
For M-bus the parameters can be configured from the
Set-up menu:
Baud rate 2400, 4800, ,9600, ,19200, 38400
Parity none/odd/even
Stop bits 1 or 2
Address 001 to 250
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is
verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature 23°C ±2°C
Input waveform 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion factor < 0·005)
Auxiliary supply voltage Nominal ±1%
Auxiliary supply frequency Nominal ±1%
Auxiliary supply waveform (if AC) Sinusoidal (distortion factor < 0·05)
Magnetic field of external origin Terrestrial flux
Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 3000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Shock 30g in 3 planes
*Maximum operating and storage temperatures are in the context of typical daily and seasonal
variation.
Mechanics
35 mm DIN rail dimensions 72,3 x 100 mm (WxH) per DIN 43880
Mounting DIN rail (DIN 43880)
Sealing IP51
Material Self-extinguishing UL 94 V-0
Volt, Amps, Power, Power factor and more
MID
2014/32/EU EC certifikat number 0120/SGS0151