3-phase electricity meter Eastron SDM54-M
A small and handy electricity meter, 3 modules wide, with Modbus, CE approved and MID certified making it suitable as a billing meter.
- Three phase 100A direct feed
- MID B+D certified
- Class B accuracy (1%)
- Bidirectional measurement for active energy and power
- Configurable pulsed output (import/export and Net kWh)
- Modbus output
- Measurement of multiple parameters
- 3 modules mounted on DIN rail
The SDM54-M measures and displays the characteristics of single-phase two-wire (1p2w) and three-phase four-wire (3p4w) power supplies, including voltage, frequency, current power, power factor, active and reactive energy, imported or or exported.
Energy is measured in terms of kWh and kVArh. Maximum power and current demand can be measured for preset periods of up to 60 minutes. The SDM54 supports max. 100A direct load per phase. The meter is designed for DIN rail mounting, with IP51 protection on the front. The meter is equipped with RS485 Modbus port. Configuration can also be done via the keypad, which is password protected.
Electrical specifications
Power: own power supply (via measured voltage)
Consumption: <1W, 8VA
Basic current: 10A
Max. current: 100A
Min. current for guaranteed error within specification: 0.5A
Starting current: 0.02A
Overcurrent: 30 x Imax for 0.01 s
L-N voltage: 100 to 289V a.c. (not for 3p3w supply)
L-L voltage: 173 to 500V a.c. (only for 3p supplies)
Frequency: 50 Hz (MID version)
Accuracy
Active energy Class 1 (IEC62053-21)/Class B (EN50470-3)
Reactive energy Class 2 (IEC62053-23)
Voltage 0.5% of the maximum value of the range
Current 0.5% of nominal
Frequency 0.2% of intermediate frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of maximum range
Apparent power (VA) ±1% of maximum range
More info, se attachments for datasheet and manual above.